S-Transform Based Traveling Wave Directional Pilot Protection for Hybrid LCC-MMC-HVDC Transmission Line

Zhang, Wei ; Wang, Dong
In: Energies, Jg. 15 (2022-06-30), S. 4802-4802
Online unknown

S-Transform Based Traveling Wave Directional Pilot Protection for Hybrid LCC-MMC-HVDC Transmission Line 

In this paper, the traveling wave protection issue of a hybrid high-voltage direct-current transmission line based on the line-commutated converter and modular multilevel converter is investigated. Generally, traveling wave protection based on voltage variation criterion, voltage variation rate criterion and current variation rate criterion is applied on hybrid high-voltage direct-current transmission lines as primary protection. There are two issues that should be addressed: (i) it has no fault direction identification capability which may cause wrong operation regarding external faults; and (ii) it does not consider the difference between line-commutated converter based rectifier station topology and modular multilevel converter based inverter station topology. Therefore, a novel traveling wave directional pilot protection principle for the hybrid high-voltage direct-current transmission line is proposed based on the S-transform. Firstly, the data processing capability of S-transform is described. Secondly, the typical traveling wave propagation process on a hybrid high-voltage direct-current transmission line is studied. Thirdly, a novel traveling wave fault direction identification principle is proposed. Eventually, based on PSCAD/EMTDC, a typical ±400 kV hybrid high-voltage direct-current transmission system is used for a case study to verify its robustness against fault location, fault resistance and fault type.

Keywords: S-transform; traveling wave; directional pilot protection; line-commutated converter and modular multilevel converter high-voltage direct-current

1. Introduction

Line-commutated converter (LCC) based high-voltage direct-current (HVDC) transmission systems have a number of advantages: large transmission capacity, low transmission loss and long transmission distance. However, the inverter converter has suffered from commutation failure issues for a long time [[1], [3]]. Due to the working characteristics of IGBT and PWM control strategy, the modular multilevel converter (MMC) based HVDC converter has no commutation failure issue [[5]]. However, the construction cost of MMC-HVDC converters is much higher than that of LCC-HVDC converters. Therefore, to acquire the advantages of LCC-HVDC converters and MMC-HVDC converters, hybrid line-commutated converter and modular multilevel converter high-voltage direct-current (LCC-MMC-HVDC) technology is utilized in actual power systems. Generally, rectifier and inverter sides adopt LCC-HVDC and MMC-HVDC converters, respectively.

Currently, traveling wave (TW) protection is widely utilized on hybrid LCC-MMC-HVDC transmission lines and based on voltage variation, voltage variation rate and current variation rate criteria [[7]]. In fact, the utilized TW protection is based on transient quantity rather than true high frequency TW quantity. There are two issues: (1) no direction identification capability. Based on single-ended transient quantity, it has no ability to identify forward or backward directions correctly. (2) Threshold issue. Threshold values are highly related to TW protection's reliability and sensitivity.

In order to overcome these issues, a number of scholars have proposed novel protection methods. Wang et al. [[9]] propose a TW directional pilot protection which is suitable for hybrid LCC-VSC-HVDC transmission lines. Similarly, Wang et al. [[10]] propose a novel hybrid directional comparison pilot protection scheme for the hybrid LCC-VSC-HVDC transmission line. Tang et al. [[11]] propose a novel hybrid LCC-MMC-HVDC topology which has DC transmission line fault clearance ability. Zheng et al. [[12]] propose a novel pilot protection method using the transient energy. Gijare et al. [[13]] pay attention to HVDC transmission line permanent faults in hybrid HVDC transmission systems. Wang et al. [[14]] studied hybrid HVDC transmission line boundary protection. Deng et al. [[15]] studied a single-ended TW protection principle according to full bandwidth TW in both time and frequency domains. Zou et al. [[16]] propose a novel directional pilot protection based on transient energy which is suitable for HVDC transmission lines. The above references have enough protection reliability, but the adaptability on hybrid LCC-MMC-HVDC transmission lines requires further research.

Aiming to solve these issues, this paper proposes a novel S-transform based TW directional pilot protection principle for hybrid LCC-MMC-HVDC transmission lines, which contributes in three different ways: (i) proposing a novel TW propagation characteristic analysis method of hybrid transmission systems; (ii) proposing a novel S-transform based TW directional pilot protection principle; (iii) using the whole bandwidth of the TW signal.

The rest of the paper is organized as follows. In Section 2, the principle of S-transform is introduced. In Section 3, the TW propagation process on LCC-MMC-HVDC transmission lines is studied. In Section 4, a novel S-transform based TW directional pilot protection principle is proposed. In Section 5, according to a ±400 kV hybrid LCC-MMC-HVDC simulation case based on PSCAD/EMTDC, the proposed TW protection principle's robustness against fault type, fault resistance and fault location is proved. In Section 6, a concise summary is given.

2. S-Transform Principle

S-transform is a kind of time–frequency transformation principle which has advantages over CWT and SFT algorithms [[17]]. For a signal x(t) , the result of S-transform is illustrated by

(1) W(τ,d)=+x(t)ω(τt,d)dt

where d and τ denote the flexible parameter and the time-shift coefficient, respectively; ω(τt,d) is a flexible time-shift function of the base wavelet. Since S-transform is a kind of CWT after phase angle correction, the transformation of x(t) can be described as the product of CWT itself and a phase angle modification parameter in the following:

(2) S(τ,f)=ei2πfτW(τ,d)

where f and i respectively represent the time frequency and the imaginary unit. Taking Equation (1) into Equation (2), therefore,

(3) S(τ,f)=+x(t)ω(τt,f)ei2πfτdtω(τt,f)=f2πef2(τt)2/2

where ω(τt,f) is a Gaussian window function. According to the above analysis, compared with the SFT algorithm, the Gaussian window's height and width of the S-transform algorithm vary with frequency. Therefore, the disadvantage of a fixed Gaussian window of the SFT algorithm is overcome. Defining X(f) as the Fourier transformation result of original signal x(t) ,

(4) S(τ,f)=+X(υ+f)e2π2υ2/f2+i2πτυdυ.

Then, the discrete S-transform is computed by

(5) SjT,nNT=k=0N1Xk+nNTe2π2k2/n2+i2πkj/N

where fn/NT ; τjT ; T denotes sampling time step; j,k,n=0,1,···,N1 .

The result of S-transform is an m×n order complex matrix Sm×n . The phase angle and amplitude of x(t) can be described as:

(6) SAn=angle(Sm×n)SAm=abs(Sm×n)

where SAn and SAm represent phase angle matrix and amplitude matrix, respectively.

3. Typical Transmission System

3.1. Reflection and Refraction of TW

Figure 1 presents the basic TW reflection and refraction phenomena [[18]]. As can be seen, the incident VTW ( u1 ) and CTW ( i1 ) propagate along line 1, and refraction and reflection happen at an impedance discontinuity point (generally busbar or fault point). In addition, the TW impedances at line 1 and line 2 are Z1 and Z2 , respectively. The reflection VTW and refraction VTW are u2 and u3 , respectively. The reflection CTW and refraction CTW are i2 and i3 , respectively. The forward direction of VTW is defined from transmission line to earth. The forward direction of CTW is its actual propagation direction. Hence, the reflection and refraction coefficients are obtained as

(7) λu=Z2Z1Z2+Z1λi=Z2Z1Z2+Z1βu=2Z2Z2+Z1βi=2Z1Z2+Z1

where λu and βu are VTW reflection and refraction coefficients, respectively; λi and βi are CTW reflection and refraction coefficients, respectively.

3.2. LCC-HVDC Rectifier Station

Generally, an LCC-HVDC station is applied at the rectifier side to obtain higher power transmission capacity, of which the typical topology is illustrated in Figure 2. The rectifier side includes a thyristor based converter, power transformer, relay, AC filter and DC filter. It generally adopts a constant DC current control strategy. Additionally, a large smoothing reactor is installed at the terminal of the transmission line. The wave impedances of the smoothing reactor and transmission line are described as ZSR and ZTL , respectively. Therefore, according to Equation (7), the reflection and refraction coefficients are

(8) λRu=ZSRZTLZSR+ZTLλRi=ZSRZTLZSR+ZTLβRu=2ZSRZSR+ZTLβRi=2ZTLZSR+ZTL

where λRu and λRi are VTW and CTW reflection coefficients at the rectifier station, respectively; βRu and βRi are VTW and CTW refraction coefficients at the rectifier station, respectively.

3.3. MMC-HVDC Inverter Station

An MMC-HVDC station is generally applied at the inverter side to avoid commutation failure. Figure 3 shows a typical structure of an MMC-HVDC inverter station, which comprises the IGBT based converter (including a number of SMs and bridge arm inductance), power transformer, relay and filter inductance. It generally adopts the constant DC voltage control and constant reactive power control strategies in the inverter side. After a fault occurs, the incident VTW signals arrive at the relay location. Afterwards, the refraction VTW signals pass through the converter into earth, and reflection VTW signals return to the fault location. Since the TW propagation process period is less than a few ms, the working state of the converters remains approximately unchanged. Therefore, the wave impedance of converters can be computed by

(9) ZCO=jk1ωCjk2ωC+2jωL=4πfLk1+k22πfC

where ZCO is wave impedance of the converter; ω and f respectively denote angular and time frequencies; k1 and k2 respectively represent the numbers of inserted SM capacitances of upper and lower bridge arms. Therefore, according to Equation (7), the reflection and refraction coefficients are

(10) λIu=ZCOZTLZCO+ZTLλIi=ZCOZTLZCO+ZTLβIu=2ZCOZCO+ZTLβIi=2ZTLZCO+ZTL

where λIu and λIi are VTW and CTW reflection coefficients at thw inverter station, respectively; βIu and βIi are VTW and CTW refraction coefficients at the inverter station, respectively.

4. Protection Principle

4.1. TW Propagation Characteristic in Hybrid LCC-MMC-HVDC Transmission System

Figure 4a,b provide the TW's propagation characteristics with different faults. L and R stand for rectifier side and inverter side, respectively. L1 , L2 , L3 and L4 are TW mutations at the rectifier side. R1 , R2 and R3 are TW mutations at the inverter side.

Table 1 and Table 2 describe both terminals' TW mutations under different fault types. u(t) and i(t) represent VTW and CTW signals, respectively. λLu and λLi represent the rectifier side's VTW reflection coefficient and CTW reflection coefficient, respectively. λFu and λFi represent the fault location's VTW reflection coefficient and CTW reflection coefficient, respectively. λRu and λRi represent the inverter side's VTW reflection coefficient and CTW reflection coefficient, respectively. βFu and βFi represent the fault location's VTW refraction coefficient and CTW refraction coefficient, respectively. βLu and βLi represent the rectifier side's VTW refraction coefficient and CTW refraction coefficient, respectively. uF and iF represent the initial VTW and CTW, respectively. L1 , L2 and L3 represent the different TW mutations at the rectifier side. R1 , R2 and R3 represent the different TW mutations at the inverter side. αL and αR represent the angle phase differences of VTW and CTW of the rectifier side and inverter side, respectively. Generally, 1<λLu=λLi<1 , 1<λRu=λRi<1 , 1<λFu=λFi<1 , βLu,βLi,βFu,βFi>0 . In addition, the initial VTW ( uF ) and initial CTW ( iF ) have the same polarities.

4.2. Fault Direction Identification Algorithm

Define the fault direction identification coefficient,

(11) E=j=0N1k=10MPjT,kfsPjT,kfs=AmjT,kfs×AnjT,kfsAm=absSujT,kfs×absSijT,kfsAn=angleSujT,kfsangleSijT,kfs,

where E represents the fault direction identification coefficient; jT , N and T represent sampling time, data window length and time sampling step ( j=0,1,···,N1;N=1000; T=1μ s in this paper), respectively; kfs , M and fs represent sampling frequency, maximum frequency and frequency sampling step ( k=10,11,···,M;M=500;fs=1 kHz in this paper), respectively; P, Am and An stand for instantaneous power, instantaneous amplitude and instantaneous phase angle, respectively; Su and Si represent S-transform matrixes of VTW and CTW, respectively. According to Table 1 and Table 2, based on Equation (11):

  • If it is a forward fault for the relay, the phase angle difference between VTW and CTW is approximately equal to π . In other words, the AnjT,kfs=π . Therefore, (12) E=j=0N1k=10MPjT,kfs=π×j=0N1k=10MAmjT,kfs0.
  • If it is a backward fault for the relay, the phase angle difference between VTW and CTW is approximately equal to 0. In other words, the AnjT,kfs=0 . Therefore, (13) E=j=0N1k=10MPjT,kfs=0×j=0N1k=10MAmjT,kfs0.

Based on Equations (12) and (13), the fault direction identification algorithm is expressed by:

(14) EΔforwardfaultE<Δbackwardfault

where Δ is the experience threshold value ( Δ=50 MVA·rad).

4.3. TW Protection Implementation

Figure 5 describes protection implementation, and it can be separated into several steps:

  • (i) Start.
  • (ii) Data sampling. The VTW and CTW data are sampled by a 1 MHz sampling rate, and the data window in this paper is 1 ms.
  • (iii) Phase-mode transform. In order to adapt to different fault types, the paper adopts a positive sequence to calculate (15) M1M0=1111P+P, where M1 and M0 represent positive and zero sequence signals, respectively; P+ and P are positive and negative pole signals, respectively.
  • (iv) Fault direction identification. Based on Section 4.2, the fault direction identification coefficient can be obtained. Afterwards, the fault direction is identified.
  • (v) Send/receive. Two terminals exchange fault direction identification results, generally through an optical cable.
  • (vi) Fault section identification. If the fault direction identification results of two terminals are both forward faults, the internal fault can be determined. Otherwise, an external fault can be determined.
  • (vii) End.
5. Case Studies

5.1. Simulation Model

According to Figure 6, a typical ±400 kV hybrid LCC-MMC-HVDC simulation case is established via the simulation software PSCAD/EMTDC [[19]]. For the study case, the converter topology of the LCC rectifier side and MMC inverter side are respectively illustrated in Figure 2 and Figure 3. The rectifier side adopts the constant DC current control strategy. The inverter side adopts the constant DC voltage and constant reactive power control strategies. The HVDC transmission line adopts a frequency dependent model. Meanwhile, the simulation rate is set to 1 MHz. F1, F2 and F3 represent the PG, NG and PN internal fault cases, respectively. F4 represents the PG external fault. In the simulation, the faulty signals are acquired at transmission line terminals (RP, RN, IP and IN), and afterwards the protection algorithms can proceed and respond to the fault. All the simulation parameters are refer to an actual power grid.

5.2. Typical Fault Simulation

Figure 7 shows the VTWs and CTWs of both terminals with a typical internal fault (F1). The fault occurs at F1 (30 km away from the LCC rectifier side, PG fault, 0 fault resistance). uRP and uRN are respectively the VTWs of positive and negative transmission lines of the rectifier station. uIP and uIN are respectively the VTWs of positive and negative transmission lines of the inverter station. iRP and iRN are respectively the CTWs of positive and negative transmission lines of the rectifier station. iIP and iIN are respectively the CTWs of positive and negative transmission lines of the inverter station. According to Figure 7, Figure 8 shows the positive sequence mode VTWs and CTWs of both terminals with an internal fault (F1). uR1 and iR1 are the positive sequence mode VTW and CTW of the rectifier side, respectively. uI1 and iI1 are the positive sequence mode VTW and CTW of the inverter side, respectively. In order to compare the proposed protection principle with the state-of-the-art work, comparison simulation results are illustrated.

5.2.1. The Proposed Protection Principle

Based on Figure 8, Figure 9 shows the instantaneous power of both terminals with an internal fault. As can be seen, the instantaneous power varies with different sampling times and frequencies. Accordingly, based on Equation (11), the fault direction identification coefficients of both terminals are 8004.4MVA·rad and 600.3MVA·rad , respectively. Based on Equation (14) and Section 4.3, the internal fault is determined correctly. Similarly, a typical external fault is simulated. The fault happens at F2 (near the LCC-HVDC rectifier station, PG fault, 50Ω grounding resistance). The instantaneous power is described in Figure 10. Accordingly, based on Equation (11), the fault direction identification coefficients of both terminals are 9.8MVA·rad and 365.0MVA·rad , respectively. Based on Equation (14) and Section 4.3, the external fault is determined correctly.

5.2.2. The State-of-the-Art Work

We choose [[21]] as a comparable work, of which the fault direction discrimination parameter can be described as

(16) γ=j=0N1ku(k)i(k)j=0N1i2(k)

where k is the sampling point; u(t) and i(t) are respectively the intrinsic mode functions of VTW and CTW which are obtained by an empirical mode decomposition algorithm; k is the VTW amplitude conditioning factor.

Based on Figure 8, Figure 11 illustrates the comparison chart of ku and i of both terminals with an internal fault (F1). Based on [[21]], the fault location discrimination parameters of both terminals are −0.586 and 0.0089, respectively. As can be seen, for the relay away from the fault location, the protection principle cannot act correctly.

5.3. Simulations under the Influence of Fault Location Issue

To validate the performances of the proposed TW protection method under the influence of a fault location issue, a number of cases are simulated, of which the results are provided in Figure 12 where Figure 12a–c represent the PG, NG and PN faults, respectively. Additionally, ER1 and EI1 are fault direction identification coefficients. As shown, under the influence of a fault type issue (PG fault, NG fault and PN fault) and fault location issue (0–300 km away from the converters), the proposed protection can identify fault direction correctly, implying a good reliability.

5.4. Simulations under the Influence of Fault Resistance Issue

To validate the performances of the proposed TW protection method under the influence of a fault resistance issue, a number of cases are simulated, of which the results are provided in Figure 13 where Figure 13a–c represent the PG, NG and PN faults, respectively. In addition, ER1 and EI1 are fault direction identification coefficients. As shown, under the influence of a fault type issue (PG fault, NG fault and PN fault) and fault resistance issue (0 to 300 Ω ), the proposed protection can identify fault direction correctly, implying a good reliability.

6. Conclusions

Based on S-transform, this paper proposes a novel TW directional pilot protection algorithm for a hybrid LCC-MMC-HVDC transmission line including a fault direction identification algorithm and complete implementation method. Compared with the existing literature, the performances of the proposed method have three contributions:

  • (i) The novel protection algorithm has good adaptability to a hybrid LCC-MMC-HVDC transmission line.
  • (ii) The novel protection algorithm has the ability to identify fault section information (internal and external faults) correctly. Additionally, it is not affected by factors such as fault location, fault resistance and fault type.
  • (iii) Light data exchange burden and no time synchronization pressure. Only fault direction identification coefficients are required to be transmitted via a communication channel (e.g., optical cable). In addition, no time synchronization system is required.

However, to obtain high protection reliability, it requires a data transmission channel such as an optical cable. Additionally, the adaptability of the proposed method in a hybrid HVDC system with a full bridge MMC-HVDC converter or multiterminal power grids still needs further research.

Figures and Tables

Graph: Figure 1 TW reflection and refraction.

Graph: Figure 2 Typical structure of LCC-HVDC rectifier station.

Graph: Figure 3 Typical structure of MMC-HVDC inverter station.

Graph: Figure 4 TW propagation process. (a) Internal fault. (b) External fault.

Graph: Figure 5 TW protection implementation.

Graph: Figure 6 PSCAD simulation case.

Graph: Figure 7 VTWs and CTWs of both terminals with internal fault (F1). (a) VTWs of both terminals. (b) CTWs of both terminals.

Graph: Figure 8 Positive sequence mode VTWs and CTWs of both terminals with internal fault (F1). (a) Positive sequence mode VTW and CTW of rectifier side. (b) Positive sequence mode VTW and CTW of inverter side.

Graph: Figure 9 Instantaneous power of both terminals with internal fault (F1). (a) Instantaneous power of rectifier side. (b) Instantaneous power of inverter side.

Graph: Figure 10 Instantaneous power of both terminals with external fault (F4). (a) Instantaneous power of rectifier side. (b) Instantaneous power of inverter side.

Graph: Figure 11 Comparison chart of ku and i of both terminals with internal fault (F1). (a) Rectifier side. (b) Inverter side.

Graph: Figure 12 Fault direction identification coefficients with different fault locations. (a) PG fault. (b) NG fault. (c) PN fault.

Graph: Figure 13 Fault direction identification coefficients with different fault resistances. (a) PG fault. (b) NG fault. (c) PN fault.

Table 1 Two terminals' TW mutations with internal fault.

No.Rectifier SideNo.Inverter Side

u(t)

i(t)

αL

u(t)

i(t)

αR

L1

(1+λLu)uF

(1λLi)iF

π

R1

(1+λRu)uF

(1λRi)iF

π

L2

λLuλFu(1+λLu)uF

λLiλFi(1λLi)iF

π

R2

λLuβFu(1+λRu)uF

λLiβFi(1λRi)iF

π

L3

λLu2λFu2(1+λLu)uF

λLi2λFi2(1λLi)iF

π

R3

λLu2λFuβFu(1+λRu)uF

λLi2λFiβFi(1λRi)iF

π

Table 2 Two terminals' TW mutations with external fault.

No.Rectifier SideNo.Inverter Side

u(t)

i(t)

αL

u(t)

i(t)

αR

L1

βLuuF

βLiiF

0

R1

βLu(1+λRu)uF

βLi(1λRi)iF

π

L2

λLuλFuβLuuF

λLiλFiβLiiF

0

R2

λLuλFuβLu(1+λRu)uF

λLiλFiβLi(1λRi)iF

π

L3

λLu2λFu2βLuuF

λLi2λFi2βLiiF

0

R3

λLu2λFu2βLu(1+λRu)uF

λLi2λFi2βLi(1λRi)iF

π

Author Contributions

Conceptualization, W.Z. and D.W.; methodology, W.Z.; software, W.Z.; validation, W.Z.; formal analysis, W.Z.; investigation, W.Z.; resources, D.W.; data curation, W.Z.; writing—original draft preparation, W.Z.; writing—review and editing, D.W.; visualization, W.Z.; supervision, D.W.; project administration, W.Z.; funding acquisition, D.W.; All authors have read and agreed to the published version of the manuscript.

Conflicts of Interest

The authors declare no conflict of interest.

Abbreviations

The following abbreviations are used in this manuscript:

LCCLine commutated converter
MMCModular multilevel converter
VSCVoltage source converter
HVDCHigh-voltage direct current
TWTraveling wave
IGBTInsulated gate bipolar transistor
PWMPulse width modulation
VTWVoltage traveling wave
CTWCurrent traveling wave
PGPositive pole to ground
NGNegative pole to ground
PNPositive pole to negative pole
CWTContinuous wavelet transform
SFTShort-time Fourier transform
SMSubmodule

Footnotes 1 Publisher's Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations. References Luo S.B., Gao H.L., Wang D., Zou G.B. Non-unit transient based boundary protection for UHV transmission lines. Int. J. Electr. Power Energy Syst. 2018; 102: 349-363. 10.1016/j.ijepes.2018.05.005 2 Zheng J.C., Wen M.H., Chen Y., Shao X.N. A novel differential protection scheme for HVDC transmission lines. Int. J. Electr. Power Energy Syst. 2018; 94: 171-178. 10.1016/j.ijepes.2017.07.006 3 Chen G., Hao M., Xu Z., Vaughan A., Cao J., Wang H. Review of high voltage direct current cables. CSEE J. Power Energy Syst. 2015; 1: 9-21. 10.17775/CSEEJPES.2015.00015 4 Zhang Y., Tai N., Xu B. Fault analysis and traveling-wave protection scheme for bipolar HVDC lines. IEEE Trans. Power Deliv. 2012; 27: 1583-1591. 10.1109/TPWRD.2012.2190528 5 Huang Q., Zou G.B., Wei X.Y., Sun C.J., Gao H.L. A non unit line protection scheme for MMC-based multi-terminal HVDC grid. Int. J. Electr. Power Energy Syst. 2019; 107: 1-9. 10.1016/j.ijepes.2018.11.008 6 Xiao H.Q., Xu Z., Wang S.J., Liu S., Jiang W. Control strategy for multi-infeed MMC-based HVDC system connected to weak grid. Proceedings of the 2017 IEEE Power Energy Society General Meeting. Chicago, IL, USA. 16–20 July 2017: 1-5 7 Jin X.F., Song G.B., Ma Z.B. A novel pilot protection for VSC-HVDC transmission lines based on parameter identification. Proceedings of the 12th IET International Conference on Developments in Power System Protection (DPSP 2014). Copenhagen, Denmark. 31 March–3 April 2014: 1-6 8 An W., Wei C.Z., Mou M., Huang W.F., Jin X., Ye H. Simulation and analysis of the control and protection performance for a multi terminal VSC-HVDC system. Proceedings of the 13th International Conference on Development in Power System Protection 2016 (DPSP). Edinburgh, UK. 7–10 March 2016: 1-4 9 Wang D., Hou M.Q., Gao M.Y., Qiao F. Travelling wave directional pilot protection for hybrid HVDC transmission line. Int. J. Electr. Power Energy Syst. 2019; 107: 615-627. 10.1016/j.ijepes.2018.12.028 Wang Y., Zhang B.H. A novel hybrid directional comparison pilot protection scheme for the LCC-VSC hybrid hvdc transmission lines. Proceedings of the 13th International Conference on Development in Power System Protection 2016 (DPSP). Edinburgh, UK. 7–10 March 2016: 1-6 Tang G., Xu Z. A LCC and MMC hybrid HVDC topology with DC line fault clearance capability. Int. J. Electr. Power Energy Syst. 2014; 62: 419-428. 10.1016/j.ijepes.2014.04.045 Zheng X.D., Tai N.L., Yang G.L., Ding H.Y. A transient protection scheme for HVDC transmission line. IEEE Trans. Power Deliv. 2012; 27: 718-724. 10.1109/TPWRD.2011.2179321 Gijare P.P., Tade S.V. Protection of permanent faults on DC overhead lines in hybrid converter based HVDC system. Proceedings of the 2015 International Conference on Energy Systems and Applications. Pune, India. 30 October–1 November 2015: 302-305 Wang Y.T., Zhang B.H. Study on the transmission line boundary characteristics of the hybrid HVDC system. Proceedings of the 2016 IEEE PES Asia Pacific Power and Energy Engineering Conference (APPEEC). Xi'an, China. 25–28 October 2016: 1311-1315 Deng F., Li X.R., Zeng X.J. Single-ended travelling wave protection algorithm based on full waveform in the time and frequency domains. IET Gener. Transm. Distrib. 2018; 12: 3680-3691. 10.1049/iet-gtd.2017.1730 Zou G.B., Huang Q., Song S.L., Tong B.B., Gao H.L. Novel transient-energy-based directional pilot protection method for HVDC line. Prot. Control. Mod. Power Syst. 2017; 2: 159-168. 10.1186/s41601-017-0047-z Li Z., Zou G.B., Du T., Yang W.J. S-transform based pilot protection method for hvdc transmission lines. Proceedings of the 2015 5th International Conference on Electric Utility Deregulation and Restructuring and Power Technologies (DRPT). Changsha, China. 26–29 November 2015: 1667-1672 Wang D., Gao H.L., Luo S.B., Zou G.B. Travelling wave pilot protection for LCC-HVDC transmission lines based on electronic transformers' differential output characteristic. Int. J. Ofelectrical Power Energy Syst. 2017; 93: 283-290. 10.1016/j.ijepes.2017.06.004 Krishna T.N.V., Sathishkumar P., Himasree P., Punnoose D., Raghavendra K.V.G., Himanshu, Naresh B., Rana R.A., Kim H.J. 4T Analog MOS Control-High Voltage High Frequency (HVHF) Plasma Switching Power Supply for Water Purification in Industrial Applications. Electronics. 2018; 7245. 10.3390/electronics7100245 Krishna T.N.V., Himasree P., Rao S.S., Kumar Y.A., Kundakarla N.B., Kim H.J. Design and Devel-opment of a Digital Controlled Dielectric Barrier Discharge (DBD) AC Power Supply for Ozone Generation. J. Sci. Ind. Res. 2020; 79: 1057-1068 Wang D., Gao H.L., Luo S.B., Zou G.B. Ultra-high-speed travelling wave protection of transmission line using polarity comparison principle based on empirical mode decomposition. Math. Probl. Eng. 2015; 2015: 1-9. 10.1155/2015/195170

By Wei Zhang and Dong Wang

Reported by Author; Author

Titel:
S-Transform Based Traveling Wave Directional Pilot Protection for Hybrid LCC-MMC-HVDC Transmission Line
Autor/in / Beteiligte Person: Zhang, Wei ; Wang, Dong
Link:
Zeitschrift: Energies, Jg. 15 (2022-06-30), S. 4802-4802
Veröffentlichung: MDPI AG, 2022
Medientyp: unknown
ISSN: 1996-1073 (print)
DOI: 10.3390/en15134802
Schlagwort:
  • Control and Optimization
  • Renewable Energy, Sustainability and the Environment
  • Energy Engineering and Power Technology
  • Building and Construction
  • Electrical and Electronic Engineering
  • Engineering (miscellaneous)
  • S-transform
  • traveling wave
  • directional pilot protection
  • line-commutated converter and modular multilevel converter high-voltage direct-current
  • Energy (miscellaneous)
Sonstiges:
  • Nachgewiesen in: OpenAIRE
  • File Description: application/pdf
  • Rights: OPEN

Klicken Sie ein Format an und speichern Sie dann die Daten oder geben Sie eine Empfänger-Adresse ein und lassen Sie sich per Email zusenden.

oder
oder

Wählen Sie das für Sie passende Zitationsformat und kopieren Sie es dann in die Zwischenablage, lassen es sich per Mail zusenden oder speichern es als PDF-Datei.

oder
oder

Bitte prüfen Sie, ob die Zitation formal korrekt ist, bevor Sie sie in einer Arbeit verwenden. Benutzen Sie gegebenenfalls den "Exportieren"-Dialog, wenn Sie ein Literaturverwaltungsprogramm verwenden und die Zitat-Angaben selbst formatieren wollen.

xs 0 - 576
sm 576 - 768
md 768 - 992
lg 992 - 1200
xl 1200 - 1366
xxl 1366 -