This paper investigated the characteristics of a novel type of hybrid high voltage direct current (HVdc) converter, which is composed by line commutated converter series with voltage source converter. The system and valve level control strategies are introduced, which can provide ac system voltage support. A novel filter design scheme composed by resonant filers for hybrid HVdc are also proposed, which can decrease the capacity of reactive power compensation equipment without deteriorate harmonic characteristics. The ac voltage of HVdc fluctuation level caused by transmitted power variation will be effectively reduced, with the coordination between filter design scheme and converter control. In addition, the influence of ac grid strength is also analyzed by equivalent source internal impedance represented by short circuit ratio (SCR). Finally, the +800 kV/1600 MW hybrid HVdc system connecting two ac grids under different SCR cases are studied, and the PSCAD/EMTDC simulation results have validated the effectiveness for proposed strategy.
Keywords: high voltage direct current (HVdc); line commutated converter (LCC); voltage source converter (VSC); control strategy; filter design; short circuit ratio (SCR)
The high voltage direct current (HVdc) system has been widely applied in large bulk energy long distance transmission scenarios. At present, the converters for practical HVdc engineering projects adopted can be divided into two types [[
Comprehensively, LCC-HVdc is more competitive in the field of maturity and cost efficiency, while VSC-HVdc has higher operation flexibility and ability for extreme weak system operation. However, LCC-HVdc is lack of the islanded operation and voltage support ability, which requires synchronous sources and large bulk reactive power compensation devices at ac side. Unlike LCC-HVdc, VSC-HVdc can transmit power to islanded system and provide reactive power support without auxiliary devices. Moreover, the LCC-HVdc has commutation failure problem, which threats the safety operation of ac system dramatically, which do not exist for VSC-HVdc. Therefore, establishing a hybrid HVdc converter combining the advantages of two different converters has aroused extensive attention. In fact, two planning engineering projects: Wudongde ±800 kV UHVdc [[
The hybrid LCC-VSC HVdc scheme can also be divided into two types: different converter station combination and single converter with hybrid topology. The former has plenty schemes, including LCC rectifier combing with VSC inverter, which can avoid inverter side commutation failure problem [[
The latter hybrid scheme is firstly proposed in [[
It can be concluded that the previous researches mainly considered the serial hybrid HVdc topology dc system operation and fault characteristics, without enough investigation for the ac system interaction with serial hybrid HVdc, especially for the series problems brought by extreme weak ac system connection. For the traditional Cigre benchmark filter scheme adopted in former researches, large bulk reactive power is generated under fundamental frequency, which is not appropriate for the serial hybrid converter with voltage support ability. Thus, the control strategy and novel filter design scheme for serial hybrid HVdc is proposed to support the weak ac system operation. Meanwhile, the change of ac system equivalent impedance also has a marked impact on the ac side electrical component harmonics and voltage fluctuation level, which requires more investigation.
The rest of this paper is organized as follows, the characteristics of serial VSC-LCC hybrid HVdc is investigated, based on the mathematical models of LCC and MMC in the first section. The next section provides the detailed control strategy for hybrid HVdc, containing both the system and valve level. In Section 4, the resonant filter design scheme is compared with the traditional Cigre Benchmark scheme by both the frequency-domain impedance, power loss as well as reactive power compensation capacity. After that, the influence of grid strength is also investigated by equivalent Thevenin circuit with different short circuit ratio (SCR). In the final section, the simulation cases built in PSCAD/EMTDC platform have proved the effectiveness of proposed strategy and filter design scheme, and the ac voltage fluctuation level under transmitted power changing is reduced dramatically.
The structure of hybrid HVdc is shown in Figure 1, the upper converter utilizes a LCC, while the lower utilizes HB-MMC-based VSC, because IGBT insulation tolerance is weaker compared with thyristor. For both rectifier and inverter, LCC is series with VSC. It is noteworthy that the figure only showed the positive pole of HVdc, and the negative pole is symmetric.
By installing thyristor-based bypass circuit breaker (TCB) switches and mechanical bypass circuit breaker (MCB), there are four typical operation modes for hybrid HVdc as Figure 2 shown. The thyristor bypass switch is composed of antiparallel thyristors, and the status is controlled by the thyristor firing angle.
For large-scale renewable energy integration scenario, the active power input fluctuates due to the intermittence and randomness of radiance and wind velocity. If the active power is extremely low (such as lower than 0.1 p.u.), LCC may operate in discontinuous current mode (DCM), which will cause consistent valve overvoltage. Therefore, hybrid HVdc operation modes should be switch the between mode 1 and mode 2, which is realized by the TCB control.
The topology of 12 pulses LCC is shown in the Figure 3, and according to the quasi-steady state formula, LCC rectifier mathematical model can be expressed as:
(
where U
The rectifier commutation angle μ
(
Similarly, the inverter mathematical model can be expressed as:
(
Also, the inverter commutation angle μ
(
where γ
(
and α
According to KVL, rectifier and inverter dc voltage have relationship as:
(
Normal LCC control strategy applied constant extinction angle (CEA) for inverter and constant current (CC) for rectifier. If the sending grid and receiving grid have enough strength which can guarantee the ac voltage stable, the operation point of LCC can be easily determined. However, when the LCC is connected with weak grid or islanded grid, the interaction between HVdc and ac grid will be more complicated and new strategy is required. Meanwhile, for islanded grid without synchronous sources, pure LCC-HVdc is impossible to run only if the islanded grid can provide phase angle reference and voltage support.
In most VSC-HVdc projects, HB-MMC topology is used due to its low harmonic, low power losses as well as high reliability comparing with two level VSC. HB-MMC equivalent circuit is shown in the Figure 4, where C
(
where j denotes the phase a, b, c, N is the total number of submodules per arm, and S
(
where P
In general, the rectifier side LCC controls the dc current and inverter side LCC controls the extinction angle for pure LCC-HVdc projects. For the serial hybrid HVdc topology, it is noteworthy that LCC rectifier and inverter have already determined the operation point, so only dc voltage of VSCs can be controlled. Therefore, both rectifier and inverter side VSCs can be set as constant dc voltage (Edc control) mode for hybrid HVdc system. Although VSCs can also be operated at active power mode, Edc control is preferred due to the better dc voltage dynamic responses.
Rectifier LCC applies dc current with backup firing angle control, as shown in Figure 5. The dc current order Idc_rec is received from inverter side, and PI controller regulates the firing angle to track Idc_rec for normal condition. The firing angle is limited between 5° and 150°, and the control mode will be automatic changed to constant firing angle if PI controller output has reached the limit value.
LCC inverter control applies constant extinction angle (CEA) with backup constant current (CC) and current margin control (CMC), which is shown in Figure 6. The maximum value selector decides the control mode for LCC inverter. Normally, CEA mode is enabled to decrease the reactive power consumption, and CMC can eliminate the firing angle fluctuation caused by harmonic distortion. I
In this paper, VSC topology is selected as HB-MMC, and its control strategy included valve level control and converter level. The former is composed by staircase modulation mode and voltage balancing algorithm, and the latter contained power out loop, current inner loop and circulating current suppression control (CCSC). The VSC converter level control strategy is shown in Figure 7, which applied dc voltage and ac voltage out loop. PLL denotes phase lock loop, which can track the grid voltage phase angle for coordinate transformation, and the reference rotation axis is set as ac voltage d-axis component. The reactive power control loop contains three PI controller in series, which regulate ac voltage, reactive power output and q-axis current, respectively. The inner current loop adopts feedforward compensation control to enhance the dynamic response, where L denotes the arm inductance. With the implementation of ac voltage outer loop, the VSC reactive power output can be regulated according to the ac voltage level, which is crucial for the safe operation of hybrid serial HVdc. Meanwhile, by changing the number of compensated capacitor banks in Section 4.2, the coordinated strategy can maintain the reactive power exchange between hybrid HVdc and ac system in a reasonable range.
Considering the fact that LCC brings 11th, 13th, and other (12k ± 1)th harmonics into ac grids, passive filters are equipped necessarily for the harmonics elimination. For pure LCC-HVdc, paralleled capacitors with damping branch are applied to eliminate characteristic harmonics and provide reactive power compensation. The typical damping capacitor structure are shown in Figure 8, whose parameters origin from Cigre Benchmark HVdc model at rectifier side.
The 11th and 13th damping capacitor impedance can be written as:
(
(
where s denotes the Laplace operator. The Bode diagrams of damping capacitors frequency impedance and phase angle are shown in the Figure 9. It can be seen from the figure that two damping capacitor impedance reaches the minimum value at around 528 Hz and 580 Hz, which is beneficial for 11th and 13th order accompanied harmonics filtering.
The reactive power compensation Q
(
To decrease the reactive power exchange between VSC and ac system, a novel filter design scheme based on resonant filter is proposed in this section, and its structure is shown in Figure 10. The scheme can change the reactive power compensation value with switching of capacitor banks, and the characteristic harmonics are filtered by the resonant filters with small reactive power output.
The resonance branch contains the serial capacitor C
(
The bode diagram of 11th resonant filter with marked parameters is shown in Figure 11, and the impedance magnitude reaches the minimum value at resonant point around 550 Hz. Meanwhile, for 345 kV ac system, the active power consumption and reactive power generation at power frequency 50 Hz are 1.3738 MW and 38.8345 MVar, respectively. Compared with the former 11th damping filter, the reactive power compensation value is much lower, which indicates the LCC characteristic harmonics can be eliminated without massive reactive power generation.
Furthermore, the influence of resonant filter parameters is also investigated, especially for the coil resistance R
To indicate the ac system strength level, SCR is normally selected as a critical index. According to the equivalent Thevenin circuit of ac system, the change of SCR would influence the reactive power exchange value and characteristic harmonics filtering effect. Assuming the power factor of LCC is constant, and the accompanied harmonic currents are represented by paraleled current sources with constant magnitude ratio with main component. The LCC and VSC simplified models are shown in Figure 13.
LCC is simplified as a series of paralleled current sources, with the main component I
(
where s
To verify the hybrid serial LCC-VSC HVdc system, a PSCAD/EMTDC simulation case was built, and detailed parameters are listed in Table 1. Both sending grid and receiving grid were simplified as Thevenin equivalent circuit, which was same as the Cigre Benchmark HVdc model. Both sending-end and receiving-end ac systems short circuit capacity were 2500 MVA, and the nominal ac voltages were 345 kV and 230 kV, respectively. The nominal capacity of serial LCC-VSC hybrid HVdc was 1600 MW, which indicates the SCR are 1.5625 for both sending-end and receiving-end ac system. The filter was designed as mentioned above. The whole system start-up process, active power change dynamic and comparison between different SCR ac system are provided in this section, to validate the effectiveness of proposed control strategy and better performance with traditional LCC-HVdc and serial LCC-VSC hybrid HVdc with Cigre Benchmark filter design scheme.
The simulation waveforms of hybrid HVdc system start-up are shown in Figure 14a–e, respectively, including ac RMS voltage, dc voltage, dc current at rectifier side, active power and reactive power of LCC, as well as MMC.
After MMC start-up, the dc voltage for both rectifier side and inverter side maintained stable at 400 kV for the preparation of whole system startup. At t = 3.0 s, LCC inverter and rectifier trigger signals deblocked, and the dc current reference value I
Also, the total submodules voltage of MMC upper arm and lower arm in phase a during start-up is also shown in Figure 14f. The total submodules voltage fluctuated between ±5% p.u., which is acceptable for operation, and the growth of fluctuation was caused by the rise of power output.
The simulation results of hybrid HVdc system with dc current reference change is shown in Figure 15, where Scheme I denots the serial hybrid HVdc with Cigre Benchmark filters, and Scheme II represents the serial hybrid HVdc with proposed filter scheme. The connected extreme weak ac systems were the same with 5.1, whose SCR values were both 1.5625. At t = 9.0 s, dc current reference value I
Comparing the ac system rms value curves for both rectifier side and inverter side, scheme I voltage fluctuated in a wider range than scheme II, which indicates the filter scheme proposed could decrease the voltage fluctuation by active power changing better. Meanwhile, Figure 15f provides the detailed curves of reactive power exchange between ac system and hybrid HVdc. It can be directly concluded that the proposed scheme could decrease the reactive power exchange value between ac system and hybrid HVdc. It is noteworthy that the proposed scheme could also provide better damping for dynamic process as Figure 15c shown. Therefore, the comparison verified the proposed scheme had better performance comparing with serial hybrid HVdc with Cigre Benchmark filter scheme.
From the analysis in Section 4.3, the ac system strength was corelated with the reactive power exchange between ac system and hybrid HVdc converter, as well as harmonic filtering effect. Considering the above system was operated under extreme weak scenario, with SCR lower than 2.0, this section provides the comparison between three equivalent ac systems with different SCR. The three typical SCR values were selected as 1.51625, 3.0, and 5.0, respectively, which can represent the extreme weak ac system, weak ac system, and strong ac system.
The detailed parameters are shown in the Table 2, the rectifier side ac equivalent voltage U
The basic components of ac current and voltage were 1.9524 kA and 140.37 kV, respectively, with the exponential FFT. It can be seen from the figure that the characteristic harmonics at 12k ± 1-order are the main harmonic components. The magnitude of 12k ± 1-order harmonics increased slightly with the growth of SCR, which is consistent with the analysis in Section 4.3. The harmonic components in all three scenarios were pretty low, which can satisfy the requirement of ac system total harmonic distortion (THD).
The waveforms of different SCR are shown in Figure 17, including the ac RMS voltage and reactive power exchange for both rectifier and inverter side. With the dc current reference value change as Section 5.2, the voltage and reactive power exchange value adjusted. It can be seen from the picture that the growth of SCR decreased the voltage fluctuation range. The fluctuation range for all scenarios were acceptable, which indicates the serial hybrid HVdc under proposed strategy can operate for different ac systems.
This paper proposed the control strategy and filter design scheme for serial LCC-VSC hybrid HVdc, which can decrease the exchange value of reactive power and provide ac system with voltage support. The characteristics of converters are introduced based on the mathematical model, and the proposed strategy combines the voltage support ability of VSC with LCC operation mode. Foremost, the proposed filter scheme can eliminate the characteristic currents generated by LCC without providing large bulk reactive power, which is suitable for the operation of serial hybrid HVdc. Meanwhile, the influences of ac system strength is analyzed, which indicates the weaker system brings the ac voltage fluctuation range increase with the active power change. The final PSCAD/EMTDC case of hybrid +800 kV/1600 MW hybrid HVdc system connecting with two weak ac grids simulated the start-up and dc current reference change processes, which validate the effectiveness of proposed strategy. The comparison results with serial hybrid HVdc adopted Cigre Benchmark filter scheme have showed the advantage of proposed control strategy and filter scheme, especially for extreme weak ac system.
Graph: Figure 1 LCC-VSC serial hybrid HVdc structure.
Graph: Figure 2 Hybrid high voltage direct current (HVdc) operation modes. Mode 1: Both line commutated converters (LCCs) and voltage source converters (VSCs) are working; mode 2: Only VSCs are working; mode 3: Only LCCs are working; Mode 4: LCC is working on one side, and VSC is working on the other side.
Graph: Figure 3 LCC topology.
Graph: Figure 4 HB-MMC equivalent circuit.
Graph: Figure 5 Rectifier LCC control strategy.
Graph: Figure 6 Inverter LCC control strategy.
Graph: Figure 7 VSC dc and ac voltage control strategy.
Graph: Figure 8 11th and 13th damping capacitors structure of Cigre Benchmark model.
Graph: Figure 9 11th and 13th damping capacitors impedance bode diagrams.
Graph: Figure 10 Resonant filter and capacitor structure.
Graph: Figure 11 Resonant filter impedance Bode diagrams.
Graph: Figure 12 Resonant filter impedance, active power loss and reactive power compensation with different coil resistance.
Graph: Figure 13 Serial LCC-VSC hybrid HVdc simplified model with ac system connection.
Graph: Figure 14 Hybrid HVdc start-up simulation results.
Graph: Figure 15 Hybrid HVdc simulation results for dc current reference changing.
Graph: Figure 16 FFT results of ac current and voltage.
Graph: Figure 17 Proposed strategy with different short circuit ratio (SCR).
Table 1 Hybrid HVdc System Parameters.
LCC Parameters VSC Parameters Capacity 1000 MW Capacity 1000 MW dc voltage 400 kV dc voltage 400 kV ac voltage 172.8 kV ac voltage 220 kV 11th filter √ No. of cells per arm 258 13th filter √ Arm inductance 40 mH PLO Kp 10 Cell capacitor 30 mF PLO Ki 50 Circuit current CCSC Trig mode equidistant Maximum current 1.2 p.u.
Table 2 Simplified ac system equivalent Thevenin circuit parameters.
Scenario I Parameters Scenario II Parameters Scenario III Parameters 382.87 363.5 357.33 215 222 225 Z_rec/Ohm 47.655 Z_rec/Ohm 23.8275 Z_rec/Ohm 15.885 Ph_rec/Deg 84 Ph_rec/Deg 84 Ph_rec/Deg 84 Z_inv/Ohm 21.2 Z_inv/Ohm 10.6 Z_inv/Ohm 7.066 Ph_inv/Deg 75 Ph_inv/Deg 75 Ph_inv/Deg 75
Conceptualization, F.C. and Z.W.; Methodology, F.C.; Validation, F.C. and L.X.; Formal Analysis, F.C.; Investigation, Z.W., L.X. and F.C.; Writing—Review & Editing, F.C.; Supervision, Z.W. All authors have read and agreed to the published version of the manuscript.
This paper is supported by State Grid Science and Technology Foundation "NY71-19-037: Research on power transmission of large-scale renewable power bases by VSC-LCC hybrid HVdc".
The authors declare no conflict of interest.
By Fan Cheng; Lijun Xie and Zhibing Wang
Reported by Author; Author; Author